karen@brightsparkelectrician.co.uk

01892 531 728

kitchen dining room

Where Bright Ideas

Come to Life!

How often do the Electrical Regulations say that a Electrical Installation Condition Report is required?

How often is an Electrical Installation Condition Report (EICR) required?

 

Electrical Regulations
Electrical installations should be Inspected and Tested as follows:

The table below provides guidance on the frequency of formal inspections of electrical installations as well as routine checks. (Table extracted from BS7671 IET Wiring Regulations 18th Edition: 2018).

Type of Installation

Routine check

Maximum period between
inspections and testing
as necessary

General Installation

   

Domestic accommodation -
general
Domestic accomomdation -
rented houses and flats

-

1 year

change of occupancy/10 years
change of occupancy/5 years

Residential accommodation (Houses of
Multiple Occupation) - halls of residence,
nurses accommodation, etc.

1 year

change of occupancy/5 years

Educational establishments

6 months

5 years

Industrial

1 year

3 years

Commercial

1 year

Change of occupancy/5 years

Offices

1 year

5 years

Shops

1 year

5 years

Laboratories

1 year

5 years

Hospitals and Clinics

   

Hospitals and medical clinics -
general areas
Hospitals and medical clinics -
medical locations

1 year

6 months

5 years

1 year

Buildings open to the public

   

Cinemas

1 year

1-3 years

Church installations

1 year

5 years

Leisure complexes
(excluding swimming pools)

1 year

3 years

Places of public entertainment

1 year

3 years

Restaurants and hotels

1 year

5 years

Theatres

1 year

3 years

Public houses

1 year

5 years

Village halls/Community centres

1 year

5 years

Special and specific installations
(for medical locations see above)

   

Agricultural and horticultural

1 year

3 years

Swimming pools

4 months

1 year

Caravans
Caravan parks

1 year
6 months

3 years
1 year

Highway power supplies

as convenient

6-8 years

Marinas

4 months

1 year

Fish farms

4 months

1 year

Emergency lighting

daily/monthly

3 years

Fire alarms

daily/weekly

1 year

Launderettes

monthly

1 year

Petrol filling stations

1 year

1 year

Construction site installations

3 months

3 months

 

 

For further Information, please do not hesitate to contact us.

Telephone: 01892 531728

Email: karen@brightsparkelectrician.co.uk

 

Related Articles

We are very pleased with Phillip’s work. You’ve truly gone above and beyond to deliver what we had in mind for our front porch.

Maria - Tonbridge

Terry did a nice job. More importantly my wife said, “He can come here any time.” Praise indeed!

Peter, Langton Green

Karen and her team of electricians are super responsive, very professional, and I love how they book an exact time and appointment with a follow-up confirmation text and email. I feel very confident in the quality of workmanship and know they will go out of their way to fix any electrical issues in my home!

Lottie - Tunbridge Wells

The two guys from Bright Sparks arrived promptly as arranged. Took their outdoor boots off before making their way to the job - a nice touch . Efficient, pleasant; I could not have asked for more. When the invoice arrived I was also pleasantly surprised. Overall a good experience 10/10

Els, Sevenoaks

I have always found Karen and her team at Bright Spark to be friendly, professional and reliable. Their quotes have been reasonably priced and provide a thorough breakdown of costs for replacements parts and labour. I highly recommend them.

Martin, Speldhurst

REQUEST QUOTE